This website or its third party tools use cookies, which are necessary to its functioning and required to achieve the purposes illustrated in the cookie policy. If you want to know more or withdraw your consent to all or some of the cookies, please refer to the cookie policy. By closing this banner, scrolling this page, clicking a link or continuing to browse otherwise, you agree to the use of cookies..

Interface CF2 for load monitoring and control

Interface CF2 for load monitoring and control
ORDERING CODE
EK-CF2-TP
DESCRIPTION

Interface for load monitoring and control that can be used for:

- the instantaneous current measurement absorbed by (up to) three single-phase electrical circuits or one three-phase electrical circuit;
- the control of electrical loads with priority detachment (and re-attachment).

The current measurement is carried out by connecting up to three EK-TA -... current transformers. Load control includes a configurable load limit threshold at which the device detaches, by priority, electrical loads connected to output channels of KNX actuators. The device is powered by the KNX bus line with a SELV voltage 30 Vdc and does not require auxiliary power. Mounting in wall box or on 35 mm rail (EN 60715) with the support EK-SMG-35 included in the delivery. To be used in KNX installations for home and building automation.


FUNCTIONS / CHARACTERISTICS
• Connection of EK-TA-... current transformers through 3 physical inputs
• Possibility of measuring of (up to) 3 single-phase lines or 1 three-phase line
• Possibility to receive the power value (W) from the bus
• 8 power thresholds (W) for generic uses (e.g. activation of loads dependent on the generation of electricity from a photovoltaic system)
• 4 logic functions (AND, OR o XOR) with 4 inputs

LOAD MONITORING
• Indirect measurement of instantaneous current (mA) through EK-TA-... transformers
• Calculation of instantaneous power (W and kW)
• Counting of the total electric energy (kWh)
• Sending on the bus measured values of current, power and energy

LOAD CONTROL
• Possibility to manage independently up to 8 loads for each measuring channel
• Power thresholds (W) for load management and corresponding hysteresis (W) settable separately for each measuring channel
• Sending on the bus of threshold overrun signal
• Possibility of selective exclusion from the bus of loads to be controlled
• Delay time (s) for load deactivation and reactivation settable separatately for each channel
CONFIGURATION AND COMMISSIONING
A detailed description of the parameters can be found in the application manual of the device. Configuration and commissioning require ETS4 2.0 or later versions. ETS application program: APEKCF2TP##.knxprod (## = release). Available languages: English, French, German, Italian